NEC Table 310.16 for copper and aluminium, all three temperature columns, with the small-conductor breaker caps marked.

How many amps can 12 gauge wire carry?

12 AWG copper is rated 25 A at 75°C in NEC Table 310.16 — but NEC 240.4(D) caps the breaker at 20 A for general use, so 20 A is the working answer.

The same small-conductor rule limits 14 AWG copper to 15 A and 10 AWG to 30 A, whatever the ampacity table says. Above 10 AWG the cap no longer applies and the table value governs.

Table 310.16 assumes no more than three current-carrying conductors in a raceway at 30°C ambient. Both change the answer downward: at 40°C a 75°C conductor derates to 88%, and four to six conductors in one raceway derate to 80%. Those factors multiply.

NEC Table 310.16 ampacity, 30°C ambient, not more than 3 current-carrying conductors
SizeCu 60°CCu 75°CCu 90°CAl 75°CMax breaker, 240.4(D)
14 AWG15 A20 A25 A—15 A (Cu)
12 AWG20 A25 A30 A20 A20 A (Cu)
10 AWG30 A35 A40 A30 A30 A (Cu)
8 AWG40 A50 A55 A40 A—
6 AWG55 A65 A75 A50 A—
4 AWG70 A85 A95 A65 A—
3 AWG85 A100 A115 A75 A—
2 AWG95 A115 A130 A90 A—
1 AWG110 A130 A145 A100 A—
1/0 AWG125 A150 A170 A120 A—
2/0 AWG145 A175 A195 A135 A—
3/0 AWG165 A200 A225 A155 A—
4/0 AWG195 A230 A260 A180 A—
250 kcmil215 A255 A290 A205 A—
300 kcmil240 A285 A320 A230 A—
350 kcmil260 A310 A350 A250 A—
500 kcmil320 A380 A430 A310 A—

Conditions this table assumes

Table 310.16 figures apply to not more than three current-carrying conductors in a raceway, cable or direct burial, at an ambient of 30°C (86°F). Change either and the numbers change:

Picking the right column

Use the column matching the lowest temperature rating anywhere in the circuit — conductor, breaker, lug or device. Most modern breakers and devices are rated 75°C. Some residential equipment, and anything marked 60°C only, pulls you to the 60°C column regardless of the wire.

THHN is a 90°C conductor, but you rarely get to use the 90°C column for sizing, because it almost always terminates on something rated lower. The 90°C column's main use is as the starting point for derating calculations, where you may derate from 90°C down and still land above the 75°C value.

Aluminium

Aluminium carries roughly 78% of copper's ampacity at the same size, so you typically go two sizes up to match: 4/0 aluminium is about equivalent to 2/0 copper. For large feeders and service entrances it is substantially cheaper and very widely used.

What matters with aluminium is the terminations. Use connectors and devices rated for it (marked AL or CU-AL), apply antioxidant compound where specified, and torque to the manufacturer's figure with a torque screwdriver — aluminium creeps under pressure, and a loose aluminium connection is the classic cause of an overheating lug.

Common questions

How many amps can 12 AWG wire carry?

25 A at 75C per Table 310.16, but NEC 240.4(D) limits the breaker to 20 A for general use, so 20 A is the practical answer.

How many amps can 6 AWG copper carry?

65 A at 75C, 55 A at 60C, 75 A at 90C. No small-conductor cap applies above 10 AWG.

Is aluminium wire safe?

Modern aluminium building wire in the larger sizes is safe and standard for feeders and services. It needs terminations rated for aluminium, correct torque, and antioxidant where specified. The historical problems were with small-gauge aluminium branch circuits and connectors not designed for it.

Does conduit in an attic change the ampacity?

Yes. Ampacity is rated at 30C ambient, and an attic can be far hotter. At 40C a 75C conductor derates to 88% of the table value, and at 50C to 75%.